Compact, up to 200 plates.

Model F is a brazed plate heat exchanger made of corrugated stainless steel plates, vacuum-brazed with copper into a single sealed block. With 10 to 200 plates and 1” ¼ connections, it covers heat pumps, chillers, economizers and district heating substations.

Tech specs

ParameterValue
Max. number of plates200
Volume per channel0.116 litres
Max. flow rate17 m³/h
Operating temperature−196 / +200 °C
Max. allowable pressure at 200 °C31 bar
Chevron anglesM – H
Heat exchange area(n−2) × 0.066 m²

Operating pressures and applications

SeriesApplicationPressure
DM1Water-water (District heating | Substations)16 bar
DM2Water-water (District heating | Substations)31 bar
DS2Steam-water31 bar
DBE2Evaporator (Chillers | Ground Source HP)31 bar
DBC2Condenser (Economizer for suction gas HE)31 bar
DBE3Evaporator (Chillers | Ground Source HP)45 / 49 bar
DBC3Condenser (Economizer for suction gas HE)45 / 49 bar

Materials and construction

FeatureDetail
PlatesStainless steel AISI 316L / 304, corrugated
BrazingCopper (Cu 99.9%), vacuum furnace
SealingGasket-free, hermetically sealed block
Connection size27 mm (1” ¼)
Connection typesThreaded (standard), soldered, inner threaded, welded, Victaulic®
AccessoriesBrackets, stud bolts, adapters, polyurethane insulation shells (on request)
Evaporator distributorFlexible distribution system, customisable to the application
ProductionPolidoro Group, Schio (Italy)

→ Plate geometry

Chevron angles, tuned to your duty.

Model F is available with M, H plates. M: mixed geometry, a balance between heat transfer and pressure drop. H: high chevron angle, more turbulence and the highest heat transfer coefficient, for tight approach temperatures (<3 K).

The trade-off is a higher pressure drop than low-angle plates, which is why every heat exchanger is configured on your operating point.

Mixed geometry plate

Chevron M

Balanced performance

High chevron angle plate

Chevron H

High heat transfer

→ Dimensions

Sizes and weights.

Ref.DimensionValue
AHeight535 mm
BWidth125 mm
CHeight hole distance471 mm
DWidth hole distance64 mm
EDepth12.53 + 2.18·n mm (DM1 | DM2 | DBE2 | DBC2)
15.92 + 2.20·n mm (DBE3 | DBC3)
FConnectors27 mm
—Weight2.995 + 0.190·n kg (DM1 | DM2 | DBE2 | DBC2)
5.506 + 0.210·n kg (DBE3 | DBC3)
—Heat exchange area(n−2) × 0.066 m²
n = number of plates

→ Applications

Where Model F works.

The applications this heat exchanger is used in. Each one has its own page, with design data, functions and applicable series.

Polidoro research and development center

→ Why Davhex

Thermal expertise, made in Italy.

Davhex is the heat exchanger division of Polidoro Group, a supplier of thermal components to OEM manufacturers.

80 years →

of experience in thermal components within Polidoro Group.

20+ years of R&D →

In-house test rooms, CFD/FEM simulation and co-development with OEM customers.

Samples, fast →

A dedicated line for prototypes and small batches, without slowing series production.

Made in Schio →

Produced in Schio (Vicenza), Italy, with vacuum brazing furnaces and leak-test stations.

→ FAQ

Frequently asked questions.

Quick answers on Model F, from construction and connections to sizing and sampling.

What is a brazed plate heat exchanger?

A compact heat exchanger made of corrugated stainless steel plates (AISI 316L / 304) brazed together with copper (Cu 99.9%) in a vacuum furnace. The result is a single hermetically sealed block, with no gaskets.

How many plates does Model F have, and how do I choose?

Model F is available from 10 to 200 plates. The right number depends on the power, temperatures and allowable pressure drop of your application: send us your operating data and our technical team will size the heat exchanger.

What is the difference between the series?

DM is for water-water duties (district heating, substations); DBE is the evaporator version and DBC the condenser version; DS is the steam-water version. The number indicates the pressure class: 1 = 16 bar, 2 = 31 bar, 3 = 45 bar at 135 °C / 49 bar at 110 °C.

What is Model F used for?

District heating substations, chiller and ground-source heat pump evaporators, condensers, economizers and suction gas heat exchangers, and steam duties.

What are the operating limits?

Operating temperature from −196 to +200 °C. Maximum pressure from 16 bar (DM1) to 45 bar at 135 °C / 49 bar at 110 °C (DBE3 and DBC3), depending on the series.

Can I request a sample?

Yes. Polidoro runs a dedicated line for samples and small batches, so prototypes can be supplied without waiting for series production. Use the contact form below.

Which connection types and accessories are available?

Connections are threaded as standard; soldered, inner threaded, welded and Victaulic® versions are also available. On request we supply brackets, stud bolts, adapters and polyurethane insulation shells.

How do I size the heat exchanger?

Use the Davhex selection software, available on davhex.com after licence activation: it gives the optimal sizing for your project. For dedicated versions or custom distributors, our technical team can run specific tests.

→ Related models

Compare the range.

Other Davhex brazed plate heat exchangers for similar duties.

Model D

10 to 200 plates, 1” ¼ connections: DHW, data centers, heat pumps and chillers.

View model →

Model G

10 to 300 plates, 2” ½ connections: the largest model, for substations and data centers.

View model →

Model B

6 to 60 plates, 22 mm connections. Also suited to ground-source heat pump evaporators.

View model →